AGL50-EV 7
3 - Environment
3.1 Environmental Conditions
Installation location ��������������������� Pollution degree 2 or lower (free from direct sunligth, vibration, dust, corrosive or inammable
gases, fog, vapour oil and dripped water, avoid saline environment)
Installation altitude ���������������������� Max 2000m (3281 feet) above sea level; above 1000m a current reduction of 1.2% for every
100m (328 feet) of additional height applies.
Mechanical conditions for installation ������� Vibrational stress: EN 60721-3-3 Class 3M1
Operation temperature ������������������ -10…50°C (14°…122°F). At above 40°, 2% derating for each °C, at 50°, 20% derating.
Air humidity (operation) ������������������ 5 % to 85 %, 1 g/m
3
to 25 g/m
3
without moisture condensation or icing (Class 3K3 as per
EN50178)
Air pressure (operation) [kPa] ������������� 86 to 106 (Class 3K3 as per EN50178)
Drive shall operate under environmental service conditions (climatic, mechanical, pollution, ...) dened in
EN61800-2 as for “usual service conditions”.
3.2 Storage and transport
Temperature:
storage ������������������������������ -20…+55°C (-4…+131°F), (class 1K4 as per EN50178)
transport ����������������������������� -20…+60°C (-4…+140°F), class 2K3 as per EN50178,
Air humidity :
storage ������������������������������ 5% to 95 % (Class 1K3 as per EN50178)
transport: ���������������������������� 95 % (3) 60 g/m (4)
A light condensation of moisture may occur for a short time occasionally if the device is not in
operation (class 2K3 as per EN50178)
Air pressure:
storage ������������������������������ [kPa] 86 to 106 (class 1K4 as per EN50178)
transport ����������������������������� [kPa] 70 to 106 (class 2K3 as per EN50178)
(3) Greatest relative air humidity occurs with the temperature @ 40°C (104°F) or if the temperature of the device is brought suddenly from
-25 ...+30°C (-13°...+86°F).
(4) Greatest absolute air humidity if the device is brought suddenly from 70...15°C (158°...59°F).
3.3 Standard
General standards ���������������������� EN 61800-1, IEC 143-1-1.
Safety ������������������������������� EN 50178, EN 61800-5-1, UL508C,UL840 (PD2, OV3)
Climatic conditions ���������������������� EN 60721-3-3, class 3K3. EN 60068-2-2, test Bd.
Clearance and creepage ����������������� EN 50178, UL508C, UL840. Overvoltage category for mains connected circuits: III; degree of
pollution 2
Vibration ����������������������������� EN 60068-2-6, test Fc.
EMC compatibility ���������������������� EN 12015 (with optional external EMI lter), EN 12016
Rated input voltages �������������������� IEC 60038
Protection degree ���������������������� IP20 according to EN 60529
IP54 for the cabinet with externally mounted heatsink.
Approvals ����������������������������� CE according to LVD directives 2014/35 / EC and EMC 2014/30 / EC.