32 AGL50-EV
7.4 Startup Menu
Lift version has parameters that are organized with access levels, as follows:
Access level Accessible parameters
1 - Basic display parameters
- Command for save parameters
- P.998
2 (Default) - All level 1 parameters
- Startup parameters
- All commands
3 All parameters
The access level is set by the parameter P.998 Param access lev.
Note! .
When using GFeXpress, congurator, all parameters are accessible, regardless of what is specied by pa-
rameter P.998.
In order to make drive installation easy, all the parameters needed for standard setup are gathered in the STARTUP
menu. This menu consists of links to parameters present in different drive menus. Therefore, making a change to any of
the parameters in Startup, is equivalent to make the same change to the linked parameter in another menu.
The list of parameters in Startup menu of the lift version follows:
Note!
(*) = Size dependent
(ALIAS): On STARTUP menu only. Parameter code of same parameter on other menu .
Menu S - Startup
Code Display (Description) Def. Min. Max
S.000 Mains voltage (linked to P.020) 380 230 480
Nominal voltage (Vrms) of the AC input mains.
S.001 Mains frequency (linked to P.021) 50 50 60
Nominal frequency (Hz) of the AC input mains.
S.100 Base voltage (linked to P.061) 380 50 528
Maximum inverter output voltage (Vrms). It should be set to motor rated voltage, as shown on the nameplate.
S.101 Base frequency (linked to P.062) 50 25 500
Motor base frequency (Hz). It is the frequency at which the output voltage reaches the motor rated (data on motor nameplate).
S.150 Motor rated curr (linked to P.040) (*) (*) (*)
Motor rated current (Arms). It should be set according to motor nameplate.
S.151 Motor pole pairs (linked to P.041) 2 1 60
Number of pole pairs of the motor (data on motor nameplate).
S.152 Motor power fact (linked to P.042) (*) (*) (*)
Motor input power factor at rated current and rated voltage. It should be set according to nameplate.
S.153 Motor stator R (linked to P.043) (*) (*) (*)
Equivalent resistance of the motor stator windings (Ohm). This value is important for correct operation of the automatic boost,
and slip compensation functions. It should be set to half of the resistance measured between two of the motor input terminals,
with the third terminal open. If unknown, it can be automatically measured by the autotuning command (see S.170).
S.170 Measure stator R (linked to C.100) 0.50 0.01 5.00
The execution of this command allows the user to measure the equivalent stator resistance of the motor in use. After the
command is issued, it is necessary to initiate a standard run sequence, by giving enable and start commands. The inverter
will close the run contactor, but will not release the brake, allowing for current to ow in the windings. After the procedure is
successfully completed, the value of S.153 is automatically updated.