AGL50-EV 39
Timer1in
Timer1out
T T
T
T
T
T
Timer 1in
Timer 1 out
Tt<T
[3] On/Off delay The closure of the Input (On) is transferred on Output after pre-set time has elapsed.
The opening of the Input (Off) initiates the pre-set delay, after which the Output is reset (Off).
[4] Pulse The closure of the Input (On) is transferred immediately on the Output.
After pre-set time has elapsed, the Output reset (Off).
Timer 1in
Timer 1 out
Symmetrical flasher
TTT TTTt<T
[5] Sym asher The closure of the Input (On) is transferred immediately on the Output.
The Output cycle between On and Off for as long as Input is close (On).
The ratio is 1:1 (time On = time Off)
A.321 Timer 1 set src 0 0 27
Select input signal of Timer 1. See list of I.000
A.322 Timer 1 delay 3.00 0.00 30.00
Set delay of Timer 1. See list of I.000
Example of Timer 1 use:
The default conguration of I.100 “Dig output 1 cfg” is [51] “Contactor”.
For the needs of external sequences is necessary to delay of 3 sec the rising edge.
You can get this behaviour with the Timer 1.
The necessary congurations are:
A.320 Timer 1 mode = [1] On delay
A.321 Timer 1 set src = [26] Contactor
A.322 Timer 1 delay = 3.0 sec
I.100 Dig output 1 cfg = [78] Timer 1 out