4.4 Input electrical data
Choke ������������������������������� Sizes 1...3: Optional (DC or AC), sizes 4-5 : integrated (DC)
Size Input
voltage
Uln
Input
frequency
THD with DC
choke
Overvoltage
threshold
(Vdc)
Undervoltage
threshold
(Vdc)
Effective input current In (@ In out) DC-Link
Capacity
(Vac) (Hz) (@ In out) @ 230 Vac (A) @ 400 Vac (A) @ 480 Vac (A)) (µF)
ADL300-...-4 , 3ph
1040
three-phase
230 - 380
- 400 - 460
- 480 Vac
-15%+10%
50/60 Hz,
± 5%
< 35 %
(in accord-
ance with EN
12015)
820 Vdc
@ 480 Vac =
470 Vdc;
@ 460 Vac =
450 Vdc
@ 400 Vac =
391 Vdc;
@ 380 Vac =
371 Vdc
@ 230 Vac =
225 Vdc
12 11 10 470
1055 17 16 15 680
2075 23 22 20 680
2110 31 29 26 1020
3150 42 40 37 1500
3185 50 47 45 2250
3220 55 53 50 2700
4300 55 55 49 2350
4370 72 72 65 2350
4450 89 89 81 2800
5550 97 97 89 4700
5750 136 136 122 5600
ADL300-...-2T, 3ph
2055
three-phase
200 - 230
Vac ±10%
50/60 Hz,
± 2%
< 35 %
(in accord-
ance with EN
12015)
500 Vdc
@ 200 Vac =
196 Vdc;
@ 230 Vac=
225 Vdc
31 - - 1020
3075 42 - - 1500
3110 53 - - 2700
4150 55 - - 2350
4185 72 - - 2350
4220 89 - - 2800
5300 97 - - 4700
5370 136 - - 5600
ADL300-...-2M, 1ph
1011 single-
phase
200 Vac
-10%+10%
230 Vac
-15%+10%
50/60 Hz,
± 2%
- 410 Vdc
@ 200 Vac =
196 Vdc;
@ 230 Vac =
225 Vdc
16 - - 2200
1015 18 - - 2200
2022 24 - - 4050
2030 31 - - 4050
3040 35 - - 4950
3055 50 - - 4950
4.5 Output electrical data
Maximum output voltage U2 �������������� 0.98 x Uln (Uln = AC input voltage)
Maximum output frequency f2 ������������� 300 Hz
The derating factors shown in the table below are applied to the rated DC output by the user. They are not automati-
cally implemented by the drive: Idrive = In x Kalt x Kt x Kv.
Size In Rated output current
(fsw = default)
Pn mot
(Recommended motor power ,fsw =
default)
Reduction factor IGBT brak-
ing unit
@Uln =
230Vac
@Uln =
400Vac
@Uln =
460Vac
@Uln =
230Vac
@Uln =
400Vac
@Uln =
460Vac
Kv Kt Kalt
(A) (A) (A)
(kW) (kW) (Hp)
(1) (2) (3)
ADL300-...-4, 3ph
1040 9 9 8,1 2 4 5 0.95 0.95 1.2
Standard
internal (with
external
resistor);
braking
torque 150%
MAX
1055 13.5 13.5 12.2 3 5.5 7.5 0.95 0.95 1.2
2075 18.5 18.5 16.7 4 7.5 10 0.95 0.95 1.2
2110 24.5 24.5 22 5,5 11 15 0.95 0.95 1.2
3150 32 32 28.8 7,5 15 20 0.95 0.95 1.2
3185 39 39 35.1 9 18.5 25 0.95 0.95 1.2
3220 45 45 40.5 11 22 30 0.95 0.95 1.2
4300 60 60 54 15 30 40 0.95 0.95 1.2
4370 75 75 67.5 18.5 37 50 0.95 0.95 1.2
4450 90 90 81 22,0 45 60 0.95 0.95 1.2
5550 105 105 94 30 55 75 0.95 0.95 1.2
5750 150 150 135 37 75 100 0.95 0.95 1.2
External
optional