ADL300 • Quick installation guide - Specifications and connection 73
8.2.8 Motor self-tuning
Set PAR 2024 Autotune still to On to enable motor self-tuning.
The rmware will automatically reset it to Off.
The following warning messages are displayed at the start and end of Self-tuning:
Operations displayed on the optional keypad Operations displayed on the integrated keypad
Close Enable input C EN
Open Enable input O EN
When the self-tuning procedure is executed its progress is displayed. In this phase the rst digit on the right indicates
the progress of the procedure by rotating the external segments of the display.
If an error occurs, the word Er is displayed with the error code. Press Prg to exit the error.
Note ! For further information see chapters "9.1 Asynchronous motor startup wizard" on page 81 and "9.2 Startup wizard for brushless motors on page 93 .
8.2.9 Asynchronous/Synchronous selection
• To switch from Asynchronous to Synchronous:
Menu 4 - DRIVE CONFIG, PAR 6100 Load synch control
04.88.
Enter
85.50.
61. 00.
Enter
8E nt.
Enter
Press Enter to reset the drive and restart in the new operating mode.
Note ! Important: the default parameters including the LIFT application are reloaded.
This can only be done with the drive disabled.
• To switch from Synchronous to Asynchronous:
Menu 4 - DRIVE CONFIG, PAR 6100 Load synch control
04.88.
Enter
85.50.
61. 00.
Enter
8E nt.
Enter
Press Enter to reset the drive and restart in the new operating mode.
Note ! Important: the default parameters including the LIFT application are reloaded.
This can only be done with the drive disabled.
8.2.10 Correspondence table displayed character/alphabet
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
1 2 3 4 5 6 7 8 9 0