18 ADL300 • Quick installation guide - Specifications and connection
Size In Rated output current
(fsw = default)
Pn mot
(Recommended motor power ,fsw =
default)
Reduction factor IGBT brak-
ing unit
@Uln =
200-230Vac
@Uln =
200-230Vac
@Uln =
200-230Vac
Kt Kalt
(A)
(kW) (Hp)
(2) (3)
ADL300-...-2T, 3ph
2055 24.5 - - 5.5 - 7.5 0.95 1.2
Standard
internal (with
external
resistor);
braking
torque 150%
MAX
3075 32 - - 7.5 - 10 0.95 1.2
3110 45 - - 11 - 15 0.95 1.2
4150 60 - - 15 - 20 0.95 1.2
4185 75 - - 18.5 - 25 0.95 1.2
4220 90 - - 22 - 30 0.95 1.2
5300 105 - - 30 - 40 0.95 1.2
5370 150 - - 37 - 50 0.95 1.2
External
optional
Size In Rated output current
(fsw = default)
Pn mot
(Recommended motor power ,fsw =
default)
Reduction factor IGBT brak-
ing unit
@Uln =
230Vac
@Uln =
230Vac
Kt Kalt
(A)
(kW)
(2) (3)
ADL300-...-2M, 1ph
1011 6 - - 1.1 - - 0.95 1.2
Standard
internal (with
external
resistor);
braking
torque 150%
MAX
1015 6.8 - - 1.5 - - 0.95 1.2
2022 9.6 - - 2.2 - - 0.95 1.2
2030 13 - - 3 - - 0.95 1.2
3040 15 - - 4 - - 0.95 1.2
3055 22 - - 5.5 - - 0.95 1.2
(1) Kv : Derating factor for mains voltage at 460Vac and power supply from AFE200.
(2) Kt: Derating factor for ambient temperature of 50°C (1% every °C above 45°C)
(3) Kalt: Derating factor for installation at altitudes above 1000 meters a.s.l. Value to be applied = 1.2% each 100 m increase above 1000 m.
E.g.: Altitude 2000 m, Kalt = 1.2% * 10 = 12% derating; In derated = (100 - 12) % = 88 % In
4.5.1 Derating values in overload condition
In overload conditions the output current depends on the output frequency, as shown in the gure below.
Figure 4.5.1-A: Ratio between overload/output frequency (ADL300-...-4 - ADL300-...-2T)
150
200
F out (Hz)
OL (% I)
N
150
180
F out (Hz)
OL (% I)
N
Sizes 1...3 (4...22kW) Sizes 4-5 (30...75kW)
Figure 4.5.1-B: Ratio between overload/output frequency (ADL300-...-2M)
150
200
OL (% I)N