92 ADL300 • Quick installation guide - Specifications and connection
Final check
Note! If you wish to use the inertia value calculated by the converter, you should copy the parameter value 5.4.20 CalcInertia (PAR 12020, Menu LIFT/ MECHANI-
CAL INFORMATION) in parameter 16.20 Inertia, PAR: 2240.
Menu 5.4 MECHANICAL DATA, parameter 5.4.20 CalcInertia, PAR: 12020, default=(S).
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
05 LIFT
x3
5.1 SPEED
5.2 RAMPS
5.3 LIFT SEQUENCES
5.4 MECHANICAL DATA
5.5 DISTANCE
5.4
MECHANICAL DATA
12/12 PAR: 12020
CalcInertia
4.11 kgm
2
Menu 16 SPEED REG GAINS, parameter 16.20 Inertia, PAR: 2240, default=(S).
14 MOTOR DATA
15 ENCODER CONFIG
16 SPEED REG GAINS
17 REGULATOR PARAM
18 TORQUE CONFIG
x2
16
SPEED REG GAINS
20/21 PAR: 2240
Inertia
4.11 kgm
2
Def: 4.110
Check the regulation mode setting before starting the motor and change it if necessary.
Available selections:
0 SSC control
1 Flux vector OL
2 Flux vector CL
Menu 04 DRIVE CONFIG, parameter 04.2 Regulation mode, PAR: 552, default=SSC control.
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
05 LIFT
x2
04 DRIVE CONFIG
2/19 PAR: 552
Regulation mode
SSC control
Value: SSC control