52 AGy -L
English
3.4 Input
2040 2055 2075 3110 3150 4185 4220 4300 4370 5450 5550 6750 7900 71100 71320 81600 82000
U
LN
AC Input voltage
[V]
AC Input frequency [Hz]
I
N
AC Input current for
continuous service :
- Connection with 3-phase reactor
@ 230Vac; IEC 146 class 1 [A] 7 9.5 14 * 18.2 25 * 32.5 39 55 69 84 98 122 158 192 220 275 n.a.
@ 400Vac; IEC 146 class 1 [A] 7.9 10.7 15.8 * 20.4 28.2 * 36.7 44 62 77 94 110 137 177 216 247 309 365
@ 460Vac; IEC 146 class 1 [A] 7 9.3 13.8 * 17.8 24.5 * 32.5 37 53 66 82 96 120 153 188 214 268 318
- Connection without 3-phase reactor
@ 230Vac; IEC 146 class 1 [A] 11 15.5 21.5 * 27.9 35.4 *
@ 400Vac; IEC 146 class 1 [A] 12 16.9 24.2 * 30.3 40 *
@ 460Vac; IEC 146 class 1 [A] 10.4 14.7 21 * 26.4 34.8 *
Max short circuit power without line
reactor (Zmin=1%)
[kVA]
650 850 1200 1700 2250 2700 3200 4200 5500 6400 7900 9800 12800 14500 17300 22400 27700
Overvoltage threshold (Overvoltage) [V]
Undervoltage threshold (Undervoltage) [V]
input-g
Braking IGBT Unit Standard internal
(with external resistor);
MAX Braking torque:
230 V -15% 480 V +10%, 3Ph
Type
For these types an external inductance is recommended
50/60 Hz ±5%
70% 90% 150%
440VDC (for 230VAC mains), 820VDC (for 400VAC mains),
820VDC (for 460VAC mains)
230VDC (for 230VAC mains), 380VDC (for 400VAC mains),
415VDC (for 460VAC mains)
150%
*: For the specified power sizes, the external reactor is strongly recommended
Power Supply and Grounding
1) Drives are designed to be powered from standard three phase lines that are electrically symmetrical with respect to
ground (TN or TT network).
2) In case of supply with IT network, the use of delta/wye transformer is mandatory, with a secondary three phase
wiring referred to ground.
In case of a three phase supply not symmetrical to ground, an insulation loss of one of the devices con-
nected to the same network can cause functional problem to the drive, if the use of a delta/wye transformer
is avoided.
Please refer to the following connection sample.
Safety
ground
L1
L2
L3
Earth
U1/L1
V1/L2
W1/L3
U2/T1
V2/T2
W2/T3
PE2/
All wires (including motor ground) must
be connected inside the motor terminal box
AC OUTPUT
CHOKE
AC Main Supply
AC INPUT
CHOKE
PE1/
Mains connection and inverter output
The drivea must be connected to an AC mains supply capable of delivering a symmetrical short circuit current lower or
equal to the values indicated on table. For the use of an AC input choke see chapter 4.
Note from the table the allowable mains voltages. The cycle direction of the phases is free.
Voltages lower than the min. tolerance values can cause the block of the inverter.
Adjustable Frequency Drives and AC Input filters have ground discharge currents greater than 3.5 mA. EN 50178 specifies
that with discharge currents greater than 3.5 mA the protective conductor ground connection (PE1) must be fixed type.
Caution