AGy -L 69
7 - Default lift configuration
Lift commands are part of a dedicated control word. Each command is assigned to a physical digital input terminal. All the
main commands are given from the DI on the standard regulation board (see table 7.1).
Similarly, lift digital outputs are configured to perform the most common functions needed to realize a standard application,
such as run and brake contactor control logic.
In AGy -L drives, commands are always coming from Lift Control Word. It is possible to issue the Run Fwd or Run Rev
commands from keypad, in order to simplify the startup procedure.
Frequency references are coming from the multi-speed selector, which is the required setting for most applications.
However, it is possible to use other sources for the frequency reference, such as analog inputs or Motopotentiometer.
Ramps are initialized to a standard set of jerks and acceleration/deceleration that should meet the requirements of most
low speed applications. It is possible, though not recommended, to disable the S-shape and use linear profiles (F.250 = 0).
In that case the jerk parameters will have no effect.
7.1 Command Logic
In the standard version, drive commands may come from several different sources (keypad, terminals, serial line etc.).
In the Lift version the parameter defining the source of the commands can only assume the following values:
P.000 Sel comandi src = “[0]CtrlWordOnly”
Command assignment
Setting Terminal
Enable src I.000 [2] DI 1 22 [0] False 100
[1] True
[2]DI1
[3]DI2
[4]DI3
[5]DI4
[6]DI5
[7]DI6
[8]DI7
[9]DI8
[10] DI Exp 1
[11] DI Exp 2
[12] DI Exp 3
[13] DI Exp 4
[14] AND 1
[15] AND 2
[16] AND 3
[17] OR 1
[18] OR 2
[19] OR 3
[20] NOT 1
[21] NOT 2
[22] NOT 3
[23] NOT 4
[24] FrqSel match
[25] Short Floor flg
Run Fwd src I.001 [3] DI 2 23 See list of I.000 101
Run Rev src I.002 [4] DI 3 24 See list of I.000 102
Freq Sel 1 src I.003 [5] DI 4 25 See list of I.000 103
Freq Sel 2 src I.004 [6] DI 5 7 See list of I.000 104
Freq Sel 3 src I.005 [7] DI 6 6 See list of I.000 105
Freq Sel 4 src I.006 [0] False See list of I.000 106
Ramp Sel 1 src I.007 [25] Short Floor Flg See list of I.000 107
Ramp Sel 2 src I.008 [0] False See list of I.000 108
Ext fault src I.009 [8] DI 7 5 See list of I.000 109
Alarm Reset I.010 [9] DI 8 4 See list of I.000 110
Bak pwr act src I.011 [0] False See list of I.000 111
Forced stop src I.012 [0] False See list of I.000 185
tab 010g
IPA
Drive command Source parameter
Deafult setting
Possible setting
Table 7.1 – Command assignment