AGy -L 53
English
AC Input Current
Note!
The Input current of the drive depends on the operating state of the connected motor. The tables (chapter
3.4) shows the values corresponding to rated continuous service, keeping into account typical output power
factor for each size.
3.5 AC Output
2040 2055 2075 3110 3150 4185 4221 4301 4371 5450 5550 6750 7900 71100 71320 81600 82000
Inverter Output (IEC 146 class1),
Continuous service (@ 400Vac)
[kVA] 6.5 8.5 12 16.8 22.4 26.5 32 42 55 64 79 98 128 145 173 224 277
Inverter Output (IEC 146 class 2)
150% overload for 60s (@ 400Vac)
[kVA] 5.9 7.7 10.9 15.3 20.3 24.1 29 38.2 50 58.3 72 89.2 116.5 132 157.5 204 252
P
N
mot (recommended motor output):
@U
LN
=230Vac; f
SW
=default; IEC 146 class 1
[kW] 2.2 3 4 5.5 7.5 10 11 18.5 22 22 30 37 55 55 75 90 100
@U
LN
=230Vac; f
SW
=default; IEC 146 class 2
[kW] 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 55 90 100
@U
LN
=230Vac; f
SW
=default; IEC 146 class 1
[Hp] 3 4 5 7.5 10 10 15 25 30 30 40 50 75 75 100 125 125
@U
LN
=230Vac; f
SW
=default; IEC 146 class 2
[Hp] 3 4 5 7.5 10 10 15 20 25 30 40 50 60 75 75 100 125
@U
LN
=400Vac; f
SW
=default; IEC 146 class 1
[kW] 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200
@U
LN
=400Vac; f
SW
=default; IEC 146 class 2
[kW] 4 5.5 7.5 11 15 18.5 22 30 37 45 55 55 90 90 110 160 200
@U
LN
=460Vac; f
SW
=default; IEC 146 class 1
[Hp] 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 150 200 250
@U
LN
=460Vac; f
SW
=default; IEC 146 class 2
[Hp] 5 7.5 10 15 20 20 25 30 40 50 60 75 100 125 150 200 250
U
2
Max output voltage
[V]
f
2
Max output frequency
[Hz]
I
2N
Rated output current:
@U
LN
=230-400Vac; f
SW
= default; IEC 146 class 1
[A] 9.6 12.6 17.7 24.8 33 39 47 63 79 93 114 142 185 210 250 324 400
@U
LN
=230-400Vac; f
SW
=default; IEC 146 class 2
[A] 8.7 11.5 16.1 22.5 30 35 43 58 72 85 104 129 168 191 227 295 364
@U
LN
=460Vac; f
SW
=default; IEC 146 class 1
[A] 8.3 11 15.4 23.1 29.7 34 40 54 68 81 99 124 161 183 218 282 348
@U
LN
=460Vac; f
SW
=default; IEC 146 class 2
[A] 7.6 10 14.0 21.0 27.0 31 36 50 62 74 90 112 146 166 198 257 317
f
SW
switching frequency (Default)
[kHz]
f
SW
switching frequency (Higher)
[kHz]
4-
Derating factor:
Voltage Factor K
V
at 460 Vac *
0.93 0.9
Temp. Factor K
T
for ambient temperature
Switching frequency K
F
Output-g
0.87
0.8 @ 50°C (122°F)
0.7 for higher f
sw
0.87
84
16
8
Type
0.94 x U
LN
(AC Input voltage)
500 200
*: Linear shapes for K
V
, K
T
, respectively in the ranges [400, 460] Vac, [40, 50]°C, (104, 122)°F.
The output of the drive is ground fault and phase to phase output short protected.
Nota!
The connection of an external voltage to the output terminals of the drive is not permissible! It is allowed to
disconnect the motor from the drive output, after the drive has been disabled.
The rated value of direct current output ( I
CONT
) depends on the supply voltage ( K
v
), the ambient temperature ( K
T
) and
the switching frequency ( K
F
) if higher than the default setting:
I
CONT
= I
2N
x K
V
x K
T
x K
sw
(Values of derating factor are the listed on table), with an overload capacity I
MAX
= 1.5 x I
CONT
for
60 seconds.