78 AGy -L
S.180 Car max speed (linked to A.090) 0.50 0.01 5.00
Speed of the lift car (m/s) when the inverter outputs the rated frequency.
S.200 Frequency ref 0 (linked to F.100) 10.0 -F.020 F.020
See description of S.207.
S.201 Frequency ref 1 (linked to F.101) 50.0 -F.020 F.020
See description of S.207.
S.202 Frequency ref 2 (linked to F.102)
S.203 Frequency ref 3 (linked to F.103)
S.204 Frequency ref 4 (linked to F.104)
S.205 Frequency ref 5 (linked to F.105)
S.206 Frequency ref 6 (linked to F.106)
S.207 Frequency ref 7 (linked to F.107) 0.0 -F.020 F.020
Frequency references (Hz) of the inverter. The selection of any of the above references is performed by the dedicated
selectors (Freq Sel 0 to 4). Although only 8 references are present in the startup menu, it is possible to use up to 16 different
references, available in the menu F.
S.220 Smooth start frq (linked to F.116) 2.0 -F.020 F.020
Frequency reference (Hz) used during the smooth start procedure.
S.225 Ramp factor 1 (linked to A.091) 1.00 0.01 2.50
Ramp accel/decel and jerks are defined by the parameters described below. However, for an easy setting, it is possible to
use a common extension factor to speed-up or slow down the ramps. For example, if S.225 is set to 0.5, all the parameters
related to the sets 1 and 3 of ramps (accels, decels and jerks) are halved, resulting in slower ramps.
S.226 Ramp factor 2 (linked to A.092) 1.00 0.01 2.50
Same as S.225, but it applies to the ramp sets 2 and 4.
S.230 Jerk acc ini 1 (linked to F.251) 0.50 0.01 10.00
Jerk (m/s
3
) applied at the beginning of an acceleration with ramp set 1 (Ramp set 1 is the one used by default, during normal
operation).
S.231 Acceleration 1 (linked to F.201) 0.60 0.01 5.00
Linear acceleration (m/s
2
) with ramp set 1.
S.232 Jerk acc end 1 (linked to F.252) 1.40 0.01 10.00
Jerk (m/s
3
) applied at the end of an acceleration with ramp set 1.
S.233 Jerk dec ini 1 (linked to F.253) 1.40 0.01 10.00
Jerk (m/s
3
) applied at the beginning of a deceleration with ramp set 1.
S.234 Deceleration 1 (linked to F.202) 0.60 0.01 5.00
Linear deceleration (m/s
2
) with ramp set 1.
S.235 Jerk dec end 1 (linked to F.254) 1.00 0.01 10.00
Jerk (m/s
3
) applied at the beginning of a deceleration with ramp set 1.
S.240 Jerk acc ini 2 (linked to F.255) 0.50 0.01 10.00
Jerk (m/s
3
) applied at the beginning of an acceleration with ramp set 2 (Ramp set 2 is the one used by default when a short
floor is detected).
Code Display (Description) Def. Min. Max