6.7.1 Use of actual value and set value inputs as digital
inputs
The actual value and set value inputs can be used as digital
inputs under the following conditions:
Control
system
Operating
mode
Setvalueinputas
digital input "in W"
Actual value input as
digital input "in X"
Positioner AUTO
3
Positioner MANUAL
3 3
Process
controller
AUTO
Process
controller
MANUAL
3
8mA 11mA
High
Low
In order to address the two digital inputs "In W" and "In X" a
resistor (R=1.2KΩ±5%) must be connected in series with the
input according to the wiring diagram. The switching levels are
> 11mA for a High-Signal and < 8mA for a Low-Signal.
Specialwiring–Useofsetvalueinputasdigitalinput
"In W"
Plug Pin Signalname Wiring
X3 1 I+, set value input
internal
24 V DC voltage
(e.g. digital output PLC)
external
-
+
GND
R=1.2KΩ±5%
Pv=1W
X3 2 I-, set value input
Specialwiring–Useofactualvalueinputasdigitalinput
"In X"
Plug Pin Signalname Wiring
X3 3 I+, actual value input
internal
24 V DC voltage
(e.g. digital output PLC)
external
-
+
GND
R=1.2KΩ±5%
Pv=1W
X3 4 I-, actual value input
6.8 Digitalinputs(optional)
The GEMÜ 1436 cPos has four digital inputs when a digital
input card is installed.
The actual value and set value inputs can be used as digital
inputs under the following conditions:
Control
system
Operating
mode
Setvalueinputas
digital input "in W"
Actual value input as
digital input "in X"
Positioner AUTO
3
Positioner MANUAL
3 3
Process
controller
AUTO
Process
controller
MANUAL
3
Use of set value input as digital input "In W"
Plug Pin Signalname Wiring
X3 2 I-, set value input
internal
High-level (14...28 V DC)
Low-level (0...8 V DC)
external
-
+
GND
X1 3 GND
Use of actual value input as digital input "In X"
Plug Pin Signalname Wiring
X3 4 I-, actual value input
internal
High-level (14...28 V DC)
Low-level (0...8 V DC)
external
-
+
GND
X1 3 GND
Digital inputs 1 and 2
Plug Pin Signalname Wiring
X1 5 Digital input 1
internal
High-level (14...28 V DC)
Low-level (0...8 V DC)
external
-
+
+
GND
High-level (14...28 V DC)
Low-level (0...8 V DC)
X1 3 GND
X3 5 Digital input 2
6.9 RS232 Interface
Plug Pin Signalname Wiring
X2 3 RxD, Receive Data
X2 4 TxD, Transmit Data
X2 5 GND
X2 : 4
X2 : 2
X2 : 3
X2 : 5
D-SUB
4
2
5
6
7
8
9
X2
X2 : 1 1
3
X2
M12 socket, B-coded, 5-pin D-SUB connector 9-pin