9.2.4 Error messages during initialisation
No. Error text Description
Condition for the occurrence of the
error
Error cause
020
Pot wrong dir
Error
The potentiometer has
recognised the wrong
control function during
initialisation.
Parameter "CtrlFn" is set to AUTO
and a valve with control function 3 is
recognised, from which the actuator has
moved in the wrong direction.
Parameter "CtrlFn" is set for a fixed
control function. This set control function
is not in accordance with the control
function determined during initialisation.
The pneumatic connections for
"CLOSED" and "OPEN" on the
valve have been switched or the
parameter "Pot Dir" is set on "fall".
The wrong control function is set.
021
Wrong function
Error
An incorrect control
function was recognised
during automatic
initialisation.
Parameter "CtrlFn" is set for a fixed
control function. This set control function
is not in accordance with the control
function determined during initialisation.
The wrong control function is
set in the "CtrlFn" parameter. If
the parameter is set to AUTO,
the 1436 cPos determines the
corresponding control function and
leaves it there (this does not apply
for control function 8 – carry out
manual initialisation in this case,
or set the parameter "CtrlFn" to
"DNO").
022
Pneumatic Error
Error
During automatic
initialisation of the valve
a pneumatic error was
detected.
The minimum stroke was undershot
End positions cannot be reached
Leakage in the system
Check the stroke of the pneumatic
system. Check leakage and end
positions.
023
Leakage
Error
During automatic
initialisation of the valve
leakage was detected.
The positioner is in initialisation mode.
Check the pneumatic system for
leakage and carry out initialisation
again.
060
TrvlSensErr
Error
A cable break or short-
circuit in the sensor
connection (travel
sensor) was detected.
Cable break or short-circuit in the
sensor connection (travel sensor)
detected.
Error text Description
Condition for the occurrence of the
error
Error cause
In 1 no Signal
No signal at digital input
In 1
Parameter In 1 is set to OFF / ON or
Safe / ON
Connect signal to digital input In 1
In 2 no Signal
No signal at digital input
In 2
Parameter In 2 is set to OFF / ON or
Safe / ON
Connect signal to digital input In 2
In W no Signal
No signal at digital input
In W
Parameter In W is set to OFF / ON or
Safe / ON
Connect signal to digital input In W
In X no Signal
No signal at digital input
In X
Parameter In X is set to OFF / ON or
Safe / ON
Connect signal to digital input In X