13 Explanation of parameters
Mode:
It is possible to choose between the operating modes AUTO(A:), MANUAL(M:), MANUAL-FLEX(F), TEST(T:) and OFF
(pause mode).
13.1 1Service
13.1.1 Scanningtheinputandoutputsignals
Service
1
SetBasics
2
SetFunction
3
SetCalibration
4
Return
6
SETUP
Communication
5
I / O Status
1.1
ActiveParaSet:
Displays the current active memory which is read o.
min-Pot-max:
Displays the minimum and maximum travel sensor position in percent. For perfect operation, this value must lie between 2 % and
98 %.
I w:
Displays the value of the current set value signal in mA.
I x:
Displays the value of the current actual value signal (when operated as a process controller).
I Out:
Displays the current value of the actual value output in mA.
W Proc X:
Displays the value of the current set value signal compared to the current actual value signal (when operated as a process
controller).
W Pos X:
Displays the value of the current set value signal compared to the current valve position in %.
Pot Abs:
Displays the current travel sensor position (Caution,thisvaluemaybedierenttothePosxvalueasthevalvedoesnot
makefulluseofthefull0-100%rangeofthetravelsensor).
Valve:
Displays the current position of the internal pilot valves (
= valve open).
Proc Ctrl In:
Displays the deviation between set value and actual value (when operated as a process controller) in %.
Proc Ctrl Out:
Displays the deviation between set value and actual value (when operated as a process controller).
If the deviation is too large, this is shown by a dot on the left-hand side or right-hand side of the display. In this case, the
controller can no longer work. All parameters on the control system route must be checked.
Pos Ctrl In:
Displays the deviation between set value and actual value (when operated as a positioner) in %.
Pos Ctrl Out:
Displays the deviation between set value and actual value (when operated as a positioner).
If the deviation is too large, this is shown by a dot on the left-hand side or right-hand side of the display. In this case, the
controller can no longer work. All parameters on the control system route must be checked.
In w:x:1:2
Displays the current conditions of the digital inputs (
= Signal High).
Relay:
Displays the current position of the internal relays K1 and K2 (
= Relay switched).