1436 cPos
17 Table for changes to the factory settings
17.1 Changed control parameters
Fields marked by X cannot be written into the individual memories but are active for all memories.
Configuration
level
Display Function P1 P2 P3 P4 Factory settings
1Service New Code: 1 Release lowest user level X X X 0
New Code: 2 Release medium user level X X X 0
New Code: 3 Release top user level X X X 0
Warnings Display warnings ON
Errors Display errors ON
SensTest Activate sensor test Disable
TAG1 Enter TAG no. 1 X X X
TAG2 Enter TAG no. 2 X X X
Configuration
level
Display Function P1 P2 P3 P4 Factory settings
2SetBasics W-Input Type of set value signal 4-20 mA
X-Input Type of actual value signal 4-20 mA p
CalPointQty
Quantity of calibration points when
initialising
9
D.Refresh Time for display refresh X X X 0.1s
DLight Setting the display lighting OnKey
AutoReturn
Time for an automatic return to the
working level
5min
HelpLanguage Text language D
HelpText Display the help text ON
Configuration
level
Display Function P1 P2 P3 P4 Factory settings
3SetFunction ProcCtrlMode Switch process controller on or off OFF
Proc-P KP amplification of the process controller 0.5
Proc-I KI reset time for the process controller 2.0s
Proc-D KD component of the process controller 0.0
Proc-T Process controller delay time 1000 ms
IxType Type of actual value filter OFF
IxTime Filter time for actual value input 0.10 s
Pos P P amplification of the positioner 1.0
Pos D D amplification of the positioner 0.0
Pos T
Decay time of the D component of the
positioner
100 ms
MinPos
Lower position for stroke limitation as a
control range
0.0 %
MaxPos
Upper position for stroke limitation as a
control range
100 %
CloseTight Lower close tight function 0 %
OpenTight Upper close tight function 100 %
DeadBand Permissible system deviation
1,0 %, K-no. 2442:
2,0 %, K-no. 2443:
5,0 %
In W
Determines the function of the digital
input "In W"
X X X OFF
In X
Determines the function of the digital
input "In X"
X X X OFF
In 1
Determines the function of the digital
input "In 1"
X X X OFF
In 2
Determines the function of the digital
input "In 2"
X X X OFF
K1 Switch Defines the type of output K1 NO
K1 Fn Determines the function of output K1 no