31 / 66
1436 cPos
13.1.2 Activating or deactivating the user access
Service
1
SetBasics
2
SetFunction
3
SetCalibration
4
Return
6
SETUP
Communication
5
I / O Status
1.1
Login
1.2
The conguration level of the GEMÜ 1436 cPos is protected in certain areas by various codes against improper changing of
parameters.
All menu items are marked by symbols indicating their write and read protection.
Example:
X-Input: 4-20 mA
0-20 mA
4-20 mA
r0w2
The following symbols are used for this purpose:
r0: no release required for reading
w0: no release required for writing
r1: lowest priority release code 1 required for reading
w1: lowest priority release code 1 required for writing
r2: medium priority release code 2 required for reading
w2: medium priority release code 2 required for writing
r3: top priority release code 3 required for reading
w3: top priority release code 3 required for writing
The codes can be changed or activated in the following menu:
Service
1
Return
Code: 0
Active Level: 3
(0...10000)
Logout?
OK
NewCode:1 1
0...10000
NewCode:2 2
0...10000
NewCode:3 3
0...10000
Login
1.2
r1w1 r1w1 r2w2 r3w3
I/O Status
1.1
Code:
Enter code for user access. The currently released user level is displayed at Active Level.
Example:
In Active Level 0 the positioner is disabled in all three user levels.
Only the parameters marked by the symbol r0w0 can be read and changed.
Logout:
Serves to log out of write protected and read protected areas in the menu. This function disables various menus depending on the
user level activated.
User level 0 is displayed in parameter Active Level.
NewCode1:
Enter the new code for the lowest user level (user level 1) (factory setting 0).
NewCode2:
Enter the new code for the medium user level (user level 2) (factory setting 0).
NewCode3:
Enter the new code for the top user level (user level 3) (factory setting 0).
Factory setting 0 means that all three codes are assigned 0. This means that all parameter menus are released.