1436 cPos
13.2 2SetBasics
Service
1
SetBasics
2
SetFunction
3
SetCalibration
4
Return
6
SETUP
Communication
5
13.2.1 Denitionofactualvalueandsetvalueinputs
W-Input:
Denes the type of set value input signal 0-20 mA / 4-20 mA.
X-Input:
Denes the type of actual value input signal 0-20 mA / 4-20 mA.
13.2.2 Reset
Default:
Serves to reset the positioner to the factory settings. All values changed by the operator are consequently deleted. An initialisation
that has already taken place will also be deleted.
Only the parameter set currently stored in the working memory is reset, however. Stored parameter sets remain unchanged (see
chapter 13.3.7).
13.2.3 Initialisation
InitValve:
Automatic or manual initialisation (adaptation of the positioner to the valve) is started.
See chapter 9.2.1 - 9.2.3.
13.2.4 Making the display settings
D.Refresh:
The time for display refresh can be changed.
DLight:
The features of the display lighting can be switched between the following settings:
OnKey – Display lighting is activated by pressing a key. The display lighting remains activated after the last key is pressed for the
period set using AutoReturn.
OnThe display lighting is permanently activated.
AutoReturn:
The time for the automatic return to the working level after last activating a key can be set. This time setting is also eective for the
display lighting (DLight).
HelpLanguage:
The help text language may be selected between D-German,
GB-English and N-Norwegian.
HelpText:
The help texts that appear as a default in the second line of the display can be masked.
If the help texts are masked, the key assignment is displayed.