SwitchingbehaviourofoutputsK1andK2whenscanningthesystemdeviationSSE:
AlarmMaxKx
AlarmMinKx
SSEmax
SSEmin
SSExTime SSExTime SSExTime
SSEminMax
13.3.6 Settingtheerrortimeanderroraction
ErrorTime:Determines the delay between error recognition and error message.
ErrorAction: Denes the behaviour of the valve if there is an error message.
Close: Valve is moved to "closed" position.
Open: Valve is moved to "open" position.
Hold: Valve remains at its current position.
Safe: Single acting valve is vented, double acting valve remains in current position.
13.3.7 Settingthetimemonitoringforwarnings
Warn. Time: Determines the delay time between warning recognition and warning message.
13.3.8 Storingparametersets
CpyParaSet:
The current positioner settings can be copied and read out in dierent memories.
It is not possible to load all changed control parameters into the programme memories. All possible storable parameters can be
found in chapter 16.4. If a parameter cannot be stored, it is active in all memories.
(P1 <= W) Write from W to P1
(P1 => P2) Write from P1 to P2
(P1 <= P2) Read from P2 to P1
(P1 => P3) Write from P1 to P3
(P1 <= P3) Read from P3 to P1
(P1 => P4) Write from P1 to P4
(P1 <= P4) Read from P4 to P1
(OFF) Storage function deactivated
P1 Memory 1
P2 Memory 2
P3 Memory 3
P4 Memory 4
W Factory settings
The GEMÜ 1436 cPos automatically stores all parameters in working memory P1.
13.3.9 Deningtheactualvalueoutput
AnalogOut:
Dening the function of the 4-20 mA actual value output.
Poti:
The actual valve position is emitted at the 4-20 mA output.
Ix:
The actual value of the process is emitted at the 4-20 mA output
(only available in the version with the integrated process controller)