Overview of initialisation parameter CtrlFn
Parameter Value Description
Automatic initialisation
function
Manual initialisation
function
4)
CtrlFn
Auto
Automatic search of the control
function during automatic
initialisation. Complies with manual
initialisation of control function 1
(NC).
Automatic detection of the
control function
Complies with NC
2)
setting.
If the valve control function
differs, do not use this
setting.
Auto NC
Control function 1 (closed by
spring force) with automatic
adaptation/modification for
automatic initialisation
Automatic detection and
modification of the control
function
Control function 1 (normally
closed)
Auto NO
Control function 2 (opened by
spring force) with automatic
adaptation/modification for
automatic initialisation
Automatic detection and
modification of the control
function
Control function 2 (opened by
spring force)
Auto DA
Control function 3 (double acting)
with automatic adaptation/
modification for automatic
initialisation
Automatic detection and
modification of the control
function
Control function 3 (double
acting)
Auto NC B
3)
Control function 1 (closed by spring
force) – for increased controller
air output (only 300 l/min) with
automatic adaptation/modification
during automatic initialisation
Automatic detection and
modification of the control
function
Control function 1 (closed by
spring force) – with increased
controller air output (only 300
l/min)
Auto NO B
3)
Control function 2 (opened by
spring force) – for increased
controller air output (only 300 l/
min) with automatic adaptation/
modification during automatic
initialisation
Automatic detection and
modification of the control
function
Control function 2 (opened by
spring force) – with increased
controller air output (only 300
l/min)
Auto DNO
1)
Control function 8 (double acting
with opening spring) – with
automatic adaptation/modification
for automatic initialisation
Automatic detection and
modification of the control
function
1)
Control function 8 (double
acting with opening spring)
DNO
1)
Control function 8 (double acting
with opening spring)
Control function 8 (double
acting with opening spring)
Control function 8 (double
acting with opening spring)
NC
2)
Control function 1 (normally
closed)
Control function 1 (normally
closed)
Control function 1 (normally
closed)
NO
2)
Control function 2 (normally open)
Control function 2 (normally
open)
Control function 2 (normally
open)
DA
2)
Control function 3 (double acting)
Control function 3 (double
acting)
Control function 3 (double
acting)
Boost NC
2) 3)
Control function 1 (closed by spring
force) – with increased controller
air output (only 300 l/min)
Control function 1 (closed by
spring force) – with increased
controller air output
Control function 1 (closed by
spring force) – with increased
controller air output (only 300
l/min)
Boost NO
2) 3)
Control function 2 (opened by
spring force) – with increased
controller air output (only 300 l/min)
Control function 2 (opened by
spring force) – with increased
controller air output
Control function 2 (opened by
spring force) – with increased
controller air output (only 300
l/min)
1)
The fixed control function setting "DNO" should be used for valves with control function 8 (double acting with opening spring). When using the "Auto DNO" setting,
a deviating control function may be incorrectly detected during an automatic initialisation and the initialisation cannot be completed. The "Wrong Function" error
message appears.
2)
Fixed control functions (NC, NO, DA, Boost NC and Boost NO) must match in terms of the actuator's control function. An incorrect assignment may lead to faults and/
or inverted action, and should therefore only be used if the correct control function is known. In case of doubt, give preference to an "auto" detection.
3)
On versions with 300 l/min flow capability (booster), double the number of pilot valves is fitted and connected in parallel. If, in these versions, a control function is set
for simple pilot valves, this leads to a reduction in the flow capability.
4)
A manual initialisation should only ever be carried out if you have not achieved satisfactory control characteristics with the automatic initialisation or this was aborted
due to an error message.