28142 Rev 15 TECHNICAL SPECIFICATIONS
Gentherm Global Power Technologies Page 10
Fuel Type: an “X” will be marked in the appropriate box to show whether the generator is
set to burn natural gas or propane. Suitable orifices are available if the TEG is to be run on
another fuel type. Please contact GPT to obtain the required orifice if you are switching fuels.
Fuel Pressure, Power, Voltage: The fuel pressure, gross power output and voltage across
the precision load have been included for reference only. These are the conditions achieved
at the Gentherm Global Power Technologies (GPT) factory before shipping. Note that the fuel
pressure is recorded in kPa and that the pressure read from the gauge must be adjusted for
the altitude.
The 5220 is operates on commercial propane, or commercial natural gas. The Fuel
Consumption of the 5220 at rated power is listed in the table below for various Fuels.
Fuel Consumption
at Rated Power
Propane Natural Gas
lb./hr* 1.30 -
gal/hr* 0.31 -
kg/hr* 0.60 -
L/hr* 1.16 -
ft
3
/hr**
11.10 29
m
3
hr**
0.31 0.82
* At 15ºC (60ºF)
** At atmospheric pressure and 15ºC (60ºF), assuming an
energy content of 37.3 MJ/m
3
or 1,000 BTU/cu. ft for natural gas
and 93.1 MJ/m
3
or 2,500 BTU/cu ft for propane.
Fuel supplied to GPT’s Thermoelectric Generators:
Shall not contain any particulates larger than 30 μm diameter, including but not limited
to sand, dust, gums, crude oil, and impurities.
Shall not have a hydrocarbon dew point more than 0ºC (32ºF) at 170 kPa
(25 PSI).
Shall not contain more than 115 mg/Sm
3
(2)
(approx. 170 ppm) of H
2
S.
Shall not contain more than 60 mg/Sm
3
(approx. 88 ppm) of Mercaptan Sulphur.
Shall not contain more than 200 mg/Sm
3
(approx. 294 ppm) of total Sulphur.