09 Maintenance User Manual V1.1-2022-12-20
No. Fault Cause Solutions
7
Grid
Underfrequency
Utility grid
exception. The
actual grid
frequency is
lower than the
requirement of the
local grid standard.
1. If the problem occurs occasionally, the
utility grid may be abnormal temporarily.
The inverter will recover automatically
after detecting that the utility grid is
normal.
2. If the problem occurs frequently, check
whether the grid frequency is within the
permissible range.
Contact the local power company if the
grid frequency exceeds the permissible
range.
Modify the underfrequency
protection threshold or disable the
underfrequency protection function
after obtaining the consent of the local
power company if the grid frequency is
within the permissible range. Or close
“Grid Underfrequency” function.
8
Grid Frequency
Instability
Utility grid
exception. The
actual grid
frequency change
rate does not meet
the requirement
of the local grid
standard.
1. If the problem occurs occasionally, the
utility grid may be abnormal temporarily.
The inverter will recover automatically
after detecting that the utility grid is
normal.
2. If the problem occurs frequently, check
whether the grid frequency is within the
permissible range.
Contact the local power company if the
grid frequency exceeds the permissible
range.
Contact the dealer or the after-sales
service if the grid frequency is within
the permissible range.

Other manuals for Goodwe GW10K-ET

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe GW10K-ET and is the answer not in the manual?

Goodwe GW10K-ET Specifications

General IconGeneral
ModelGW10K-ET
Max. DC Input Voltage1000 V
Number of MPPTs2
Rated AC Output Power10000 W
Max. AC Output Power11000 VA
Frequency50 Hz / 60 Hz
Efficiency98.3%
Dimensions516 x 415 x 180 mm
Weight25 kg
Max. DC Input Power13000 W
Start Voltage180 V
MPPT Voltage Range200V - 1000V
Number of MPP Trackers2
Max. Short Circuit Current per MPPT15 A
Nominal AC Output Power10000 W
Max. AC Apparent Power11000 VA
Nominal AC Voltage230 V / 400 V
Nominal Grid Frequency50 Hz / 60 Hz
THDi<3%
DC SwitchYes
Protection ClassIP65
Operating Temperature Range-25°C to +60°C
Cooling MethodNatural Convection
Rated Output Power10000 W
Grid Frequency50 Hz / 60 Hz
Max. Efficiency98.3%
Noise Level<30 dB
Protection DegreeIP65
TypeThree Phase
AC Voltage Range180V - 280V
Power Factor0.8 leading - 0.8 lagging
Rated Grid Voltage230 V