G16 Smoke Density Monitor
Ver.2.4 – Revision March 2022 27
Figure 6-5: Transceiver Address Settings
Press ZERO button to change unit address to the desired one, e.g. address 1 and 2. Release
ZERO button and check if the address is as wanted. When the address set- ting is correct,
press and hold the SPAN button until all signal strength LEDs are ON.
All transceivers are set with address 1 at factory. If the system is configured with 2 trans-
ceiver/reflector units, one of the transceivers must be set to address 2.
Address 3-15 are currently not in use. Go to next step – save new settings.
Note
Unit address will always appear shortly when the transceiver is connected to power
supply.
6.1.4 Save New Settings
To save the new address settings, first press and hold SPAN (see note below) and immedi-
ately after SPAN, press and hold ZERO buttons. Wait approximately 5 seconds until all
signal strength LEDs are ON. Then release the buttons.
Note
There is a risk that the transceiver counts at the address, if you press SPAN and ZERO
buttons simultaneously.