G16 Smoke Density Monitor
Ver.2.4 – Revision March 2022 27
Figure 6-5: Transceiver Address Settings
Press ZERO button to change unit address to the desired one, e.g. address 1 and 2. Release
ZERO button and check if the address is as wanted. When the address set- ting is correct,
press and hold the SPAN button until all signal strength LEDs are ON.
All transceivers are set with address 1 at factory. If the system is configured with 2 trans-
ceiver/reflector units, one of the transceivers must be set to address 2.
Address 3-15 are currently not in use. Go to next step – save new settings.
6.1.4 Save New Settings
To save the new address settings, first press and hold SPAN (see note below) and immedi-
ately after SPAN, press and hold ZERO buttons. Wait approximately 5 seconds until all
signal strength LEDs are ON. Then release the buttons.