G16 Smoke Density Monitor
Ver.2.4 – Revision March 2022 37
Figure 6-16: System Setup
The menu displays the software version of the control and monitoring unit. It also has
Home button to go back to the home menu.
The following parameters of the system can be configured in this menu:
Sensor Count
The sensor count is the total number of the transceiver/reflector units to be con- trolled.
Analog out
Analog output signals can be configured as follows:
Range
Setting
0% opacity = 4 mA
100% opacity = 20 mA
0% opacity=4 mA
0% opacity = 20 mA
100% opacity = 4 mA
0% opacity=20 mA (default)
Digital out
The alarm digital output signals can be configured as follows:
Output Signal at Active Warning or Alarm
Setting
Alarm active = Relay not energized
Alarm inactive = Relay energized
Error/Warn=OFF (default)
Alarm active = Relay energized Alarm in-
active = Relay not energized
Error/Warn=ON