8.7.5 External setpoint influence (4.1.3)
Fig. 40 External setpoint influence
Description
The function allows you to adapt the setpoint by letting measuring
parameters influence the setpoint. Typically an analog signal from
a flow or temperature transmitter, or a similar transmitter. For an
overview of transmitter types and possible positions, see
installation and operating instructions for Control MPC.
As an example, the setpoint can be adapted to parameters that
can influence the outlet pressure or temperature of the system.
The parameters which influence the performance of the system
are shown as a percentage from 0 to 100 %. They can only
reduce the setpoint, as the influence as a percentage divided with
100 is multiplied with the setpoint:
Actual setpoint (SP) = selected setpoint x influence (1) x
influence (2) x etc.
The influence values can be set individually.
A low-pass filter ensures smoothing of the measured value which
influences the setpoint. This results in stable setpoint changes.
Setting range
0-100 % signal
Inlet pressure
Outlet pressure
External pressure
Diff. pressure, external
Diff. pressure, pump
•Flow rate
Tank level, outlet side
Tank level, suction side
Return-pipe temp., external
Flow-pipe temperature
Return-pipe temperature
Differential temperature
Ambient temperature
Differential temperature.
Setting via the operating panel
Settings > Primary controller > External setpoint influence >
Input value to be influenced by. A list of available parameters
appears.
1. Select the parameter which is to influence the setpoint.
2. Press [Back].
3. Set the influence function. See section 8.7.6 Setting of
influence function (4.1.3.2).
4. Set the number of points.
5. Set: External input value (Point 1).
6. Set as a percentage: Reduce setpoint to (Point 1).
7. Repeat steps 4 to 6 for all desired parameters.
8. Press [Back].
9. Set as seconds: Filter time.
10. Select: Enabled.
Factory setting
The function is disabled.
If the Multisensor function is enabled, it will have a
higher priority than the External setpoint influence
which will be overruled.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos Control MPC 2000 Series and is the answer not in the manual?

Grundfos Control MPC 2000 Series Specifications

General IconGeneral
BrandGrundfos
ModelControl MPC 2000 Series
CategoryControl Systems
LanguageEnglish

Related product manuals