EasyManua.ls Logo

Grundfos Control MPC 2000 Series - Page 62

Grundfos Control MPC 2000 Series
528 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
62
8.7.59 Measurement, inlet pressure (4.4.1.2)
Fig. 110 Measurement, inlet pressure
Description
Dry-running protection can take place by means of a pressure
transmitter measuring the inlet pressure.
You can set two levels:
Warning
Alarm + stop.
You can set restarting and resetting of alarms to be automatic or
manual.
Setting range
Selection of analog input for the function.
Inlet pressure level for "Warning".
Inlet pressure level for "Alarm + stop".
Restarting: Manual or Auto.
Setting via the operating panel
Settings > Monitoring functions > Dry-running protection >
Measurement, inlet pressure> Go to setting of analog input.
Display 8.7.30 Analog inputs (4.3.8) appears.
1. Select: Inlet pressure.
2. Press [Back].
3. Select: Enabled.
4. Select and set the level:
Warning.
Alarm + stop.
5. Select resetting: Manual or Auto.
Factory setting
The setting is done in the startup wizard and depends on the
application.
8.7.60 Measurement, tank level (4.4.1.3)
Fig. 111 Measurement, tank level
Description
Dry-running protection can take place by means of a level
transmitter measuring the level in a tank on the inlet side.
You can set two levels:
Warning
Alarm + stop.
You can set restarting and resetting of alarms to be automatic or
manual.
Setting range
Selection of analog input for the function.
Tank level for "Warning".
Tank level for "Alarm + stop".
Restarting: Manual or Auto.
Setting via the operating panel
Settings > Monitoring functions > Dry-running protection >
Measurement, tank level > Go to setting of analog input.
Display 8.7.30 Analog inputs (4.3.8) appears.
1. Set the input to "Tank level, suction side".
2. Press [Back] x 3.
3. Select: Enabled.
4. Select and set the level:
Warning.
Alarm + stop.
5. Select alarm resetting: Manual or Auto.
Factory setting
The function is disabled.
If one of the levels is not required, the level value
must be the minimum value of the inlet-pressure
transmitter. This disables the function.

Table of Contents

Related product manuals