11.7.33 Min., max. and user-defined duty (4.3.14)
Fig. 74 Min., max. and user-defined duty
Description
This function makes it possible to let the pumps run in open loop
at a set pump performance.
Setting range
The CU 351 makes it possible to change between three operating
modes:
1. Min. duty (4.3.14.1).
2. Max. duty (4.3.14.2).
3. User-defined duty (4.3.14.3).
11.7.34 Min. duty (4.3.14.1)
Fig. 75 Min. duty
Description
In all systems, apart from Control MPC-S, minimum duty is only
possible for variable-speed pumps. In Control MPC-S systems,
only the number of pumps running at 100 % speed can be set.
Setting range
Number of pumps in operation.
Speed as percentage (25 to 100 %) for variable-speed pumps.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Secondary functions with or , and press .
3. Mark Min., max. and user-defined duty with or , and
press .
4. Mark Min. duty with or , and press .
5. Mark Number of pumps in operation, min. duty with or
.
6. Set the number with or , and save with .
7. Mark Speed with or .
8. Set the value with or , and save with .
Factory setting
TM03 2351 4807
Note
For each of these modes, the number of
operating pumps and the pump performance
(speed) can be set.
TM03 2354 4807
Number of pumps in operation during min. duty: 1
Speed as percentage for variable-speed pumps: 70

Table of Contents

Other manuals for Grundfos CONTROL MPC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CONTROL MPC and is the answer not in the manual?

Grundfos CONTROL MPC Specifications

General IconGeneral
BrandGrundfos
ModelCONTROL MPC
CategoryControl Systems
LanguageEnglish

Related product manuals