3 × 440-480 V, MLE Model K
Motor size
[hp]
Recommended
[A]
Maximum
[A]
Fuse type
15 35 60
RK1, Class J or T UL listed
fuse
20 50 80
RK1, Class J or T UL listed
fuse
25 60 80
RK1, Class J or T UL listed
fuse
30 70 80
RK1, Class J or T UL listed
fuse
Branch circuit short-circuit protection
For the USA
Integral solid state short-circuit protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with the National Electrical Code and any additional local codes, or the
equivalent.
For Canada
INTEGRAL SOLID STATE SHORT-CIRCUIT PROTECTION DOES NOT PROVIDE BRANCH CIRCUIT
PROTECTION. BRANCH CIRCUIT PROTECTION MUST BE PROVIDED IN ACCORDANCE WITH THE
CANADIAN ELECTRICAL CODE, PART I.
Overload protection
Degree of overload protection provided internally by the drive, in percent of full-load current: 102 %.
96
Appendix B

Table of Contents

Other manuals for Grundfos CRE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CRE Series and is the answer not in the manual?

Grundfos CRE Series Specifications

General IconGeneral
Motor TypeAsynchronous
Enclosure ClassIP55
Insulation ClassF
SeriesCRE
Protection ClassIP55
MaterialStainless Steel
ApplicationsWater Supply, Pressure Boosting, Irrigation
Pumped liquidClean liquids
ApprovalsCE
Voltage380-415V
Connection SizeDN 32 to DN 100
EfficiencyIE3 Premium Efficiency
Power Supply3-phase
Liquid Temperature Range-10°C to +120°C
Temperature Range-10°C to +120°C