English (GB)
11
7.6 Signal cables
• Use screened cables with a cross-sectional area
of minimum 0.5 mm
2
and maximum 1.5 mm
2
for
external on/off switch, digital inputs, setpoint and
sensor signals.
• Connect the screens of the cables to frame at
both ends with good connection. The screens
must be as close as possible to the terminals.
See fig. 9.
Fig. 9 Stripped cable with screen and wire
connections
• Always tighten screws for frame connections
whether a cable is fitted or not.
• The wires in the motor terminal box must be as
short as possible.
Terminal Type Function
NC
Normally
closed
contact
Signal relay 1
LIVE or PELVC1 Common
NO
Normally
open contact
NC
Normally
closed
contact
Signal relay 2
PELV onlyC2 Common
NO
Normally
open contact
18 GND Earth
11 DI4/OC2
Digital input and
output, configurable.
Open collector:
Maximum 24 V
resistive or inductive.
19
Pt100/1000
input 2
Pt100/1000 sensor
input
17
Pt100/1000
input 1
Pt100/1000 sensor
input
12 AO
Analog output:
0-20 mA / 4-20 mA
0-10 V
9GND Earth
14 AI3
Analog input:
0-20 mA / 4-20 mA
0-10 V
1DI2
Digital input,
configurable
21
LiqTec sensor
input 1
LiqTec sensor input
white conductor
20 GND
Earth
brown and black
conductors
22
LiqTec sensor
input 2
LiqTec sensor input
blue conductor
10 DI3/OC1
Digital input and
output, configurable.
Open collector:
Maximum 24 V
resistive or inductive.
4AI1
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
2DI1
Digital input,
configurable
5+5 V
Supply to
potentiometer and
sensor
6GND Earth
A GENIbus, A GENIbus, A (+)
Y GENIbus, Y GENIbus, GND
B GENIbus, B GENIbus, B (-)
3GND Earth
15 +24 V Supply
8 +24 V Supply
26 +5 V
Supply to
potentiometer and
sensor
23 GND Earth
25 GDS TX
Grundfos Digital
Sensor output
24 GDS RX
Grundfos Digital
Sensor input
7AI2
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
TM02 1325 4402
Terminal Type Function