Activation delay
Select the activation delay, T1.
It is the time between the digital signal and the
activation of the selected function.
Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See fig. 41.
•Not active
• active with interrupt, mode A
• active without interrupt, mode B
• active with after-run, mode C.
Select the duration time, T2.
It is the time which, together with the mode,
determines how long the selected function is active.
Range: 0 to 15,000 seconds.
Fig. 41 Duration timer function of digital inputs
Factory setting
See section 30. Factory settings.
13.11 Digital inputs/outputs
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
You can select if the interface must be used as input
or output. The output is an open collector and you
can connect it to for example an external relay or
controller such as a PLC.
Fig. 42 Example of configurable digital inputs or
outputs
To set a digital input or output, make the settings
below.
Mode
You can set the digital input or output 3 and 4 to act
as digital input or digital output:
• Digital input
• Digital output.
Function
You can set the digital input or output 3 and 4 to
these functions:
TM06 4949 3415
T input
T input > T1 + T2 T input < T1 + T2
T1 T2
T1 T2
T1 T1 T2T2
T1
T1
T input
T2
Mode C
Mode B
Mode A
Digital
input
T input > T1 + T2 T input < T1 + T2
T input
T input
Pump variant Digital inputs/outputs
TPE, TPED, NBE,
NBGE, NKE, NKGE
●
TPE, TPED, NBE, NKE
Series 2000
●
Function Terminal*
Digital input/output 3, setup 10 and 16
Digital input/output 4, setup 11 and 18
TM06 4463 2315
+ 24V
DO 3/4
External
controller