10. Standard control panel
Fig. 15 Standard control panel
10.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or . The light fields on the control panel indicates
the setpoint set.
10.1.1 Pump in differential-pressure control
mode
The following example applies to a pump in an
application where a pressure sensor gives a
feedback to the pump. If you retrofit the sensor to the
pump, set it manually as the pump does not
automatically register a connected sensor.
Figure 16 shows that the light fields 5 and 6 are
activated, indicating a desired setpoint of 3 m with a
sensor measuring range from 0 to 6 m. The setting
range is equal to the sensor measuring range.
Fig. 16 Setpoint set to 3 m, differential-pressure
control
Pump variant
Fitted as
standard
Option
TPE, TPED ● -
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
--
TM05 4848 3512
Pos. Symbol Description
1
Grundfos Eye
Shows the operating status of
the pump.
See section 17. Grundfos Eye
for further information.
2-
Light fields for indication of
setpoint.
3
Up and down. Changes the
setpoint.
4
Allows radio communication
with Grundfos GO and other
products of the same type.
When you try to establish
radio communication between
the pump and Grundfos GO or
another pump, the green
indicator light in Grundfos Eye
on the pump flashes
continuously. Press on the
pump control panel to allow
radio communication with
Grundfos GO and other
products of the same type.
5
Makes the pump ready for
operation as well as starts and
stops the pump.
Start
If you press the button when
the pump is stopped, the
pump only starts if no other
functions with higher priority
have been enabled. See
section 16. Priority of settings.
Stop
If you press the button when
the pump is running, the pump
always stops. The "Stop" text
next to the button is on.
TM05 4894 3512
Pos. Symbol Description