13.6 "Proportional-pressure setup"
"Control-curve function"
You can set the curve either to quadratic or linear.
"Zero-flow head"
You can set this value in % of the setpoint. With a
setting of 100 %, the control mode is equal to
constant differential pressure.
13.7 Analog inputs
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
Set the analog input for a feedback sensor via the
Assisted pump setup menu. See section
13.41 Assisted pump setup.
If you want to set an analog input for other purposes,
you can do this manually.
You can set the analog inputs via the Setup, analog
input menu. See section 13.42 Setup, analog input.
If you perform the manual setting via Grundfos GO,
you need to enter the menu for the analog input
under the Settings menu.
Function
You can set the analog inputs to these functions:
•Not active.
Feedback sensor.
Ext. setpoint infl..
See section 13.16.1 Setpoint influence.
Other function.
Measured parameter
Select one of the parameters, such as the parameter
to be measured in the system by the sensor
connected to the actual analog input. See fig. 39.
Fig. 39 Overview of sensor locations
Unit
Available measuring units:
Pump variant
"Proportional-pressure
setup"
TPE, TPED, NBE,
NBGE, NKE, NKGE
-
TPE, TPED, NBE,
NKE Series 2000
Pump variant Analog inputs
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
Function Terminal*
Analog input 1, setup 4
Analog input 2, setup 7
Analog input 3, setup 14
TM06 2328 3914
Sensor function, measured
parameter
Pos.
Inlet pressure 1
Diff. press., inlet 2
Liquid temp. 3
Diff. press.,outlet 4
Diff. press.,pump 5
Operating mode 6
Press. 2, external 7
Diff. press., ext. 8
Storage tank level 9
Feed tank level 10
Pump flow 11
Flow, external 12
Liquid temp. 13
Temperature 1 14
Temperature 2 15
Diff. temp., ext. 16
Ambient temp. Not shown
Other parameter Not shown
Parameter Possible measuring units
Pressure bar, m, kPa, psi, ft
Level m, ft, in
Flow rate m
3
/h, l/s, yd
3
/h, gpm
Liquid temp. °C, °F
Other parameter %
PT PT PT
PT
TT
TT
TT
Q
Q
DPT
DPT DPT
LT LT
DPT DTT
1
5
24
910
7
12
816 15
313 6 14
11

Table of Contents