Example of how to use the Assisted pump setup
for setting up the pump to constant pressure:
Grundfos GO
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode "Constant pressure".
4. Read the description of this control mode.
5. Select which analog input to use as sensor input.
6. Select sensor function according to where the
sensor is installed in the system. See fig. 39.
7. Select electrical input signal according to the
sensor specifications.
8. Select measuring unit according to the sensor
specifications.
9. Set the minimum and maximum sensor values
according to the sensor specifications.
10. Set the desired setpoint.
11. Set the controller settings K
p
and T
i
. See the
recommendations in section 13.14 "Controller"
("Controller settings").
12. Type the pump name.
13. Check the summary of settings and confirm
them.
Advanced control panel
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode Const. pressure.
4. Select which analog input to be used as sensor
input.
5. Select the measured parameter to be controlled.
See fig. 39.
6. Select measuring unit according to the sensor
specifications.
7. Set the minimum and maximum sensor values
according to the sensor specifications.
8. Select electrical input signal according to the
sensor specifications.
9. Set the setpoint.
10. Set the controller settings K
p
and T
i
. See
recommendations in section 13.14 "Controller"
("Controller settings").
11. Check the summary of settings and confirm them
by pressing [OK].
13.42 Setup, analog input
This menu is only available in the advanced control
panel.
The menu guides you through the following:
Setup, analog input
• Analog inputs 1 to 3. See page 32.
• Pt100/1000 input 1 and 2. See page 33.
• Adjusting the setpoint. See page 26.
• Summary.
13.43 "Multipump setup" (Setup of
multi-pump system)
The multipump function enables the control of two
pumps connected in parallel without the use of
external controllers. The pumps in a multipump
system communicate with each other via the
wireless GENIair connection or the wired GENI
connection.
A multipump system is set via a selected pump, i.e.
the master pump, which is the first selected pump.
If two pumps in the system are configured with an
outlet-pressure sensor, both pumps can function as
master pumps and take over the master pump
function if the other fails. This provides additional
redundancy in the multipump system.
The multipump functions are described in the
following sections.
Pump variant Setup, analog input
TPE, TPED -
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
●
Pump variant "Multipump setup"
TPE, TPED, NBE,
NBGE, NKE, NKGE
●
TPE, TPED, NBE, NKE
Series 2000
●