13.18 "Pulse flowmeter setup"
You can connect an external pulse flowmeter to one
of the digital inputs in order to register the actual and
accumulated flows. Based on this, you can also
calculate the specific energy.
To enable a pulse flowmeter, set one of the
digital-input functions to Accumulated flow and set
the pumped volume per pulse. See section
13.10 Digital inputs.
Factory setting
See section 30. Factory settings.
13.19 "Ramps"
The ramps determine how quickly the motor can
accelerate and decelerate, respectively, during
start-stop or setpoint changes.
You can set the following:
acceleration time, 0.1 to 300 seconds
deceleration time, 0.1 to 300 seconds.
The times apply to the acceleration from 0 rpm to
fixed maximum speed and the deceleration from
fixed maximum speed to 0 rpm.
At short deceleration times, the deceleration of the
motor may depend on load and inertia as there is no
possibility of actively braking the motor.
If the power supply is switched off, the deceleration
of the motor only depends on load and inertia.
Fig. 52 Ramp-up and ramp-down
Factory setting
See section 30. Factory settings.
13.20 "Standstill heating"
You can use this function to avoid condensation in
humid environments. When you set the function to
"Active" and the pump is in operating mode Stop, a
low AC voltage is applied to the motor windings. The
voltage is not high enough to make the motor rotate
but ensures that sufficient heat is generated to avoid
condensation in the motor including the electronic
parts in the drive.
13.21 Motor bearing monitoring
You can set the motor bearing monitoring function to
these values:
•"Active"
•Not active
When the function is set to "Active", a counter in the
controller starts counting the mileage of the
bearings.
The counter continues counting even if the function
is changed to Not active, but a warning is not given
when it is time for replacement.
When the function is changed to "Active" again, the
accumulated mileage is again used to calculate the
replacement time.
Factory setting
See section 30. Factory settings.
Pump variant
"Pulse flowmeter
setup"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
Pump variant "Ramps"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
TM03 9439 0908
User set ramp-up User set ramp-down
Speed
Time
User set
minimum
Fixed initial ramp Fixed final ramp
User set
maximum
Fixed
maximum
0
Pump variant "Standstill heating"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
Remember to remove the drain plugs and
fit a cover over the motor.
Pump variant
Motor bearing
monitoring
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000