GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 34
In order to disable all devices with type number 00111 of Zone No.1, you need to
input in sequence the zone number 001, device code *** and device type **.
For device with type number 1265, the asterisk mark is not allowed for the type
number.
3 Example for disabling sounder circuit output (Sounder A) and F.P.E.
The address for the Sounder circuit output on the loop interface board is 240, and its
device type is 55-SounderA. The address for F.P.E. Output is 241, and its device type is
65-F.P.E. The system defaults these two outputs into zone No .0. To disable them, you
need to operate as follows:
You can disable sounder circuit output by inputting in sequence the zone number
000, device type 240 and device type 55. The panel will light the SOUNDER
FLT/DISABLE LED.
You can disable F.P.E output by inputting in sequence the zone number 000, device
type 241 and device type 65. The panel will light the F.P.E FLT/DISABLE LED.
6.3.2.2 Enabling Devices
In the screen shown in Fig. 6-16, input number 2, you can enter device enable screen as
shown in Fig. 6-18. Same as disabling devices, you can also enable a single device or
multiple devices with the same methods of disabling them.
Enable
Z000 C000 T00 NoDefine
Fig. 6-18
6.3.2.3 Disabling/Enabling Delays
Inputting number 3 in the screen shown in Fig. 6-16 can enter the screen of
disabling/enabling delays, as shown in Fig. 6-19 Here you can select to enable or
disable the system delay.
Fig. 6-19
* Delay Mode*
1. Disable
2. Enable
In the above screen, you can operate as follows: