Replacement of the rating plug
The value of the nominal current In can be changed by replacing the rating plug located on the
front face of the sentinel Energy trip unit.
Rated
current In
Reference of
the standard
rating plug
Reference
of the Meter
Plus rating
plug
Reference
of the
Harmonic
rating plug
Reference
of the
Advanced
rating plug
Reference of
the Ultimate
rating plug
400 A HWW464HSA HWW664HSA HWW484HSA HWW704HSA HWW724HSA
630 A HWW465HSA HWW665HSA HWW485HSA HWW705HSA HWW725HSA
800 A HWW466HSA HWW666HSA HWW486HSA HWW706HSA HWW726HSA
1000 A HWW467HSA HWW667HSA HWW487HSA HWW707HSA HWW727HSA
1250 A HWW468HSA HWW668HSA HWW488HSA HWW708HSA HWW728HSA
1600 A HWW469HSA HWW669HSA HWW489HSA HWW709HSA HWW729HSA
2000 A HWW470HSA HWW670HSA HWW490HSA HWW710HSA HWW730HSA
2500 A HWW471HSA HWW671HSA HWW491HSA HWW711HSA HWW731HSA
3200 A HWW472HSA HWW672HSA HWW492HSA HWW712HSA HWW732HSA
4000 A HWW473HSA HWW673HSA HWW493HSA HWW713HSA HWW733HSA
ATTENTION
The value In of the rating plug cannot exceed the maximum rated current on the front of the
circuit breaker.
The minimum value In of the rating plug depends on the size of the rating plug chosen. It is
particularly 400 A for HW1, 630 A for HW2 and 1000 A for HW4.