1696LE008146B
Replacement of the rating plug
Action Illustration
14 Connect the external
battery to the USB-C port.
15 Check that there is no
alarm or ReadyToProtect
LED on the display.
I Max 960A
120
100
80
60
40
20
%Ir IN I1 I2 I3
ATTENTION
If one of the following alarms
displays, the rating plug is
faulty.
HWF
TRIP
E009
22 April 2022
15:26:32-
E034
RATING PLUG
03/10/2022 - 18:24:05
Remove the external battery
and replace the original rating
plug or a new rating plug as
described above. If the problem
persists, contact your Hager
representative or local Hager
technical support (contact
details for your country can be
found on the Hager website).
16 Remove the external
battery.