APPENDIX A - SETTINGS
38
HIGH SPEED COOLING AND HEAT PUMP AIRFLOW (CFM)
Table 11: Cooling and Heat Pump Airflow Taps for the Factory Supplied Air Handler
Both the COOL and ADJUST taps must be set for Cooling and Heat Pump Airflow (CFM). These are the minimums required by
the Acadia Outdoor Unit.
Fan only airflow (CFM) = 63% of high speed cooling.
Low speed cooling is used only with two-stage outdoor units. (Low speed is preset to 65% of the high speed cooling airflow.)
When operating in heat pump and electric heat modes, the airflow will be whichever is greater.
The airflow (CFM) indicator light, LED2, flashes once for every 100 CFM. Example: 12 flashes = 1,200 CFM.
ELECTRIC HEAT AIRFLOW (CFM)
Table 12: Electric Heat Airflow Taps for the Factory Supplied Air Handler
The HEAT selection only controls airflow when Electric Heat is used, not for airflow during the Heat Mode.
Table 13: Delay Comfort Settings
The DELAY selection is for ramping up and down speeds for additional or not as much humidity removal during cooling.