The shunt is the current sensor for the
Link 1000
. Its 500A 50mV
rating means that when 500 Amps flows through it there is 50mV
generated across it. The millivolt signal is translated into an Amps
display in the meter. For example: A 50A load would generate 5mV
across the shunt and would be displayed as
-50
Amps. Caution: In
the diagram below, the darker wires represent primary wiring and
should be able to carry full battery load current. Size appropriately!
1234567890123456789012345678901212
1
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
23456789012345678901234567890121
2
1234567890123456789012345678901212
2345678
2345678
23
23
234567
234567
2345678
2345678
23
23
234567
234567
234
234
234
234
234
234
234
234
RED
BLUE
+
-
ORANGE
GREEN
These wires
must be a twisted
pair!!
2 Amp Fuses
(mount within 7"
of battery)
BLACK
SYSTEM POSITIVE
Connect NO
other wires di-
rectly to battery
negative or bat-
tery side of the
shunt! All cur-
rent must flow
through the
shunt!
BATTERY
SIDE
LOAD
SIDE
500A 50 mV
SHUNT
SYSTEM NEGATIVE
LOAD SIDE
WIRE BY WIRE DETAIL
BATTERY COMPARTMENT
VIOLET
Second (Starting)
battery Voltage
Sense via 2 Amp
Fuse
Cable to Link 1000