10
Installation SPIDER PL
Release
08
09/2018
ATEX directive 2014/34/EU – specific regulations for safe
operation
Relevant for SPIDER PL devices labeled with an ATEX certificate number
when operating in explosive gas atmospheres according to ATEX
Directive 2014/34/EU, the following applies:
Make sure that the device has the following label:
DEKRA 16ATEX0108X
The modules shall be installed in a suitable enclosure in accordance
with EN 60079-15 providing a degree of protection of at least IP54
according to EN 60529, taking into account the environmental
conditions under which the equipment will be used.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
The USB port shall remain disconnected.
IECEx – Certification Scheme for Explosive Atmospheres
For SPIDER PL devices labeled with an IECEx certificate number, the
following applies:
Make sure that the device has the following label:
IECEx DEK 16.0064X
The modules shall be installed in a suitable enclosure in accordance
with EN 60079-15 providing a degree of protection of at least IP54
according to EN 60529, taking into account the environmental
conditions under which the equipment will be used.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
The USB port shall remain disconnected.