Reboot the power several times.
If this does not solve, replace the module
The cause which cannot communicate has many wiring mistakes of a communication cable. When communication
does not work, please check connection of a cable first.
EH-SIO of software ver. 2.0 does not support transmission control procedure 2. If it’s configured as procedure 2, it
works with procedure 1. (EH-SIO of software ver. 1.0 is not supported Hi-Protocol mode.)
Although EH-SIO can change transmission format configuration, the transmission format configuration of
Hi-Protocol is 7-bit / even parity / 1 stop. Please set the transmission configuration of EH-SIO as 7-bit / even parity
/ 1 stop.
In the case of a task code with station No., EH-SIO does not return a negative response, even if a parity error or
framing error occurs in the request task code.