Chapter 7 System setup
7 - 9
Check flow of Simple data link mode
All participating flag
OFF?
Please check a connection part with
EH-SIO.
Please station change time and slave
response waiting time, and see a situation.
Please check the address
of data link area.
Slave participating
flag OFF?
Please check the following items.
- Setup of communication port of slave station
- Adjustment of a station No.
(Participating registration and slave station)
- Adjustment of a transmission speed
- A connection part with a slave station
- Connection of a cable
Reboot the power several times.
If this does not solve, replace the module
Supported CPU?
(Type, Version)
Connection of
communication
cable OK?
Please connect a
communication cable correctly.
The cause which cannot communicate has many wiring mistakes of a communication cable. When communication
does not work, please check connection of a cable first.
A setup of the transmission format configuration of EH-SIO should surely use 7-bit / even parity / 1 stop bit.
The capacity of an internal output changes with models of CPU. Moreover, the classification of an internal output
may not exist. (There is no area of WL in MICRO-EH / MICRO-EHV.)
Please check the internal output of a slave station and assign link area.