Installation and Setup Guide
5-16
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay
mapped to output number 2 (as programmed in *79 Menu Mode), program the following in
*80 Menu Mode:
Prompt Entry
Output Funct. # = 01 (assuming this is the first output function)
Activated By: = 3 (zone number)
Enter Zn No. = 04 (requires 2-digit zone numbers)
Output Action = 3 (continuous pulse)
Output Number = 02 (device mapped in *79 Menu Mode)
Start Output Definition mode by pressing
80 while in Data Programming mode. The
following prompts are displayed:
80 Menu Mode
PROMPT
VALID ENTRIES EXPLANATION
Output Funct. #
(00 = Quit) 01
Output Function No.
01-12 = output function number
[] to continue
Enter the output function number to be defined
(or 00 to exit).
01 A E P Trig
?00 0 0 – ZL=1
Summary Screen
[] to continue
This screen displays a summary of the current
output programming (for this example, Zone List
has been selected-this is the default screen).
A = Output Action; E = Triggering event; P =
Partition; Trig = Trigger type
NOTE: A question mark in the summary screen
indicates that the device number shown has not
been mapped. Use *79 Menu mode to map the
device.
01 Activated By:
Zone List
Activated By
0 = delete
1 = zone list
2 = zone type
3 = zone number
[] to continue
Select where the initiating event for this output
definition is to occur as follows:
0 = delete (deletes the output function and any
previous programming;-see prompt below)
1 = zone list (go to “A” prompt)
2 = zone type (go to “B” prompt)
3 = zone number (go to “C” prompt)
If you enter “0,” the following prompt appears:
Delete? Press 1 to delete this
0 = NO, 1 = YES output definition.