Menu Mode Programming
5-25
PROMPT
VALID ENTRIES EXPLANATION
90 Alm/Trbl Proc
0
Alarm/Trouble
Processing
0=none
1=Zone type has automatic
restore
2=zone type uses Misc. Fault
Delay Time and automatic
restore
[] to continue
Select desired actions for zones assigned to this
zone type.
Option 2: Select Miscellaneous Fault Delay in
field *87.
NOTE: If 6 was selected above for the Zone
Attribute, enter 0 for this prompt.
90 TRBL SOUND
0
Trouble Sounding
0= none
1= one beep every minute
2= normal trouble sound (fast
beeps)
[] to continue
Select type of sounding upon trouble conditions on
zones assigned to this zone type.
90 ALARM SOUND
0
Alarm Sounding
0=none
1= keypad sound only
2= steady siren sounding
3= pulsing siren (temporal)
[] to continue
Select type of sounding upon alarm conditions on
zones assigned to this zone type.
90 Dial Delay
0=No, 1=Yes
Dial Delay?
0=no
1=yes
[] to continue
If selected, faults on zones assigned to this zone
type will delay reporting for whatever length of
time that is selected in dial delay (*50).
90 Disp Option
1
Display Options
0 = no display
1 = display only
2 = chime only
3 = chime & disp.
[] to continue
Select whether faults on zones assigned to this
zone type are displayed at the keypad and/or
cause a chime sound.
Alarm ID: 000
Trouble ID: 000
Contact ID Report Codes
000-999 = report code
[] to continue; returns to Enter
configurable zone type number
prompt.
Enter the desired 3-digit Contact ID report codes
for faults and troubles occurring on zones assigned
to this zone type.
IMPORTANT: Make sure the code does not
conflict with existing, predefined Contact ID
report codes. See the System Communication
section for a list of standard Contact ID codes.