6-4
Signal flow
Receiving equipment Dialing equipment
Send start char ‘w’ (77h)
Send message described above
Acknowledge ACK (06h)
(Delay greater than 500ms)
Send new start char ‘w’ (77h)
Send next message if available
Acknowledge ACK (06h)
…etc
Dialer should start sending the message no more than 200ms after start char.
If no response is detected the receiver retries sending start char three times (in total
four) before hanging up.
If the receiver reads a message with checksum error it will reply with NAK (15h),
wait more than 500ms and then send a new start char (w).
The receiver can optionally send a command back to the dialer after ACK.
The command may be one byte with any content except ‘w’ (77h), ACK (06h) or NAK
(15h)..
ADEMCO Contact ID
®
ADEMCO and Robofon Contact ID
®
Reporting takes the following format:
CCCC(CCCCCC) Q EEE GG ZZZ
where:
CCCC(CCCCCC) = 4-digit or 10-digit Customer (subscriber) ID
Q = 1-digit Event qualifier, where:
E = new event , and R = restore
EEE = 3-digit (hexadecimal) Event code (see central office receiver manual
for a complete list of event codes)
GG = 2-digit Partition Number (system messages show “00”)
ZZZ = 3-digit Zone/contact ID number reporting the alarm, or user number
for open/close reports. System status messages (AC Loss, Walk Test,
etc.) contain zeroes in the ZZZ location.