6-1
SECTION 6
System Communication and
Operation
•••••••••••••••••••••••••••••••••
Panel Communication with Central Station
This system accommodates several formats for reporting alarms and other system conditions
to the Central Station. The process of a successful transmission consists of both the method
of communication between the control panel and the Central Station receiver; and the actual
way the information is sent and displayed at the Central Station.
When the panel calls the Central Station receiver, it waits to hear a “handshake” frequency
from the receiver to confirm that the receiver is on-line and ready to receive its message.
Once the panel hears the handshake it is programmed to listen for, it sends its message. The
panel then waits for a “kissoff” frequency from the receiver acknowledging that the message
was received and understood.
If the handshake frequency is not given or is not understood by the panel, the panel will not
send its message. Once the handshake frequency is received and understood by the panel,
the panel sends its message. If there is an error in the transmission (the receiver does not
receive a “valid” message), the kissoff frequency is not given by the Central Station receiver.
The panel makes a total of eight attempts to the primary telephone number and eight
attempts to the secondary telephone number (if programmed) to get a valid message through.
If the panel is not successful after its numerous attempts, the keypad displays COMM.
FAILURE (on alpha keypads) or FC (on fixed-word keypads).
Report Code Formats
The following chart indicates the types of (handshake/kissoff) frequencies that the panel
supports and the different formats that can be sent with each.
FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME
Low Speed 1400 Hz 1900Hz (10PPS) 1400 Hz Under 15 secs
3+1, 4+1, 4+2
(Standard report)
Sescoa/Rad 2300 Hz 1800Hz (20PPS) 2300 Hz Under 10 secs
3+1, 4+1, 4+2
(Standard report)
Robofon 8 See Robofon 8 paragraph later in this section for details of the format.
Express 1400–2300 Hz DTMF (10 cps) 1400 Hz Under 3 secs
4+2 (multi-frequency)
ADEMCO
Contact ID
1400–2300 Hz DTMF (10 cps)
(multi-frequency)
1400 Hz Under 3 secs
Robofon
Contact ID
2300 Hz DTMF (10 cps)
(multi-frequency)
1400 Hz Under 3 secs

Table of Contents