AQ251 SERIES BOILER RESET CONTROL PANELS
69-1974—04 34
A/C SETTINGS
a
Central A/C – Available only if no AQ158 controller is present on the network.
CYCLES/HOUR
2 / 3 / 4 / 5 / 6 4 The maximum number of times the controller will permit
the central A/C to cycle in each hour.
MIN.OFF TIME 2 to 10 (minutes) 5M The length of time that must elapse after the AC
compressor shuts off before the Aux. Out relay is permitted
to close, to energize the compressor again.
C.W.S.D. - -
32°F to 100°F (0°C to 38°C)
65°F
(18°C)
The temperature at which cold weather shutdown is
activated.
• “- -” means Off (not used).
FAN MODE AUTO / ON AUTO Selects whether or not the fan serving the A/C system
operates constantly (ON) or operates only when there is a
call for cooling (AUTO).
FAN MODE displays only if the FAN option is selected for
AUX.PUMP. See the AUX.PUMP menu option in this table.
A/C EQUIP CONFIG Central A/C – Available only if no AQ158 controller is present on the network.
ZONE A-1 to D-16 A-1 Selects the desired zone.
A/C UNIT NONE / 1 1 Defines which A/C compressor is associated with each
zone thermostat.
NOTE: At this time, only one zone of A/C can be handled
by the AQ2000 controls. The options are 1 (if the
zone uses an AQ1000TP2 programmable
thermostat and can call for cooling), or NONE.
COOLING ENABLE / DISABLE ENABLE Enables or disables the cooling functions of the zone's
programmable thermostat (AQ1000TP2).
NOTE: This item is always set to DISABLE when a non-
programmable thermostat (AQ1000TN2) is used
in the selected zone.
STATISTICS Displays the summary and Zone relay activity (hours of operation or cycles since last reset)
LAST DATA
RESET
Max. 24,855 days (68 years) 2000 JAN 01 Date of last reset formatted as YYYY MMM DD.
RESET ALL DATA
ARE YOU SURE?
YES / NO NO Selecting YES resets all of the summary and zone activity
values to zero.
BOILER FIRE
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
BOILER PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
DHW PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
AUX PUMP
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
AUX OUT
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the relay since last reset.
ZONE A-1
ACTIV
Maximum of 596,523 hours
(68 years)
0H Hours of operation of the zone's relay (e.g., zone A-1)
since last reset.
The zone Identifier is A-1 through D-16.
ENVIRACOM Not used - reserved for future use.
Modules ID: n/a n/a n/a
Table 6. Installer Menu – Equipment Setup. (Continued)
EQUIPMENT SETUP
Menu Option Range
Factory
Default Description