CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
115
Configuring the BACnet Network Settings The BACnet Feature
8.9 Configuring the BACnet Network Settings
8.9.1 Installation and Configurations
The CGW-MB can communicate with the BACnet client in an Ethernet LAN.
8.9.2 The IP Settings
The following information applies to IP settings:
You can use only the Eth1 port for connections to BACnet clients. For more details,
refer to 8.10.1 "To Configure the BACnet Settings".
Each CGW-MB is shipped with a default node number of 235.
The computer used to configure the CGW-MB must establish an IP connection to the
CLSS Gateway mainboard. Consult with a network administrator if unsure how to
make this connection.
Connecting more than one CGW-MB prior to reconfiguring the IP address will result in
an IP address conflict.