CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022 54
CGW-MB Control Features Modbus Communications
7.19.2 Enabling the Control
CGW-MB control is enabled through a web page-based configuration tool running on the
CLSS Gateway mainboard. Enable control as follows:
1. Start the web browser on a computer that is in the same IP network as the CGW-
MB.
Note: Chrome is the recommended browser.
2. Enter the following URL in the browser:
https://192.168.10.190:9443/config/index.html
3. Do the following if any security warning is shown. Otherwise, go to step 4.
• Click the Advanced link below the error message.
• Agree to proceed.
4. In the CLSS Gateway mainboard Configuration Tool page, enter the password.
5. Go to Modbus Tools in Modbus Settings.
6. Enable or disable as needed in the control functionality.
7. Read the UL Void message shown, if it is enabled.
8. Click Save.
9. Wait until the CGW-MB shows the changes.
10.Check that the changes are correct.
7.19.3 Control Commands
Using the CGW-MB you can send relevant command values to the holding registers of
Points, Panels, and Zones.
Point Commands
Panel Commands
CAUTION: UL LISTING
ENABLING CONTROL VOIDS THE UL LISTING OF THE CGW-MB.
NOTE: Refer to the
Register Mapping
section for detailed register mapping information.
Serial
No.
Command Value Holding Register
1 EnableDisableDevice 0x400 - Enable
Use Device/Module Holding Register
Address
2 EnableDisableDevice 0x500 - Disable
Use Device/Module Holding Register
Address
Serial
No.
Command Lower Byte value
Holding
Register
1 System Reset 0x0000 20001
2 Signal Silence 0x0001 20001
3 Deactivate Buzzer 0xE 20001
4 Walk Test Sounder on 0xF 20001
5 Walk Test no sounder on 0x10 20001
6 Walk test off 0x11 20001