CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022 157
FireWarden Panels Connecting to the Panels
C.6.5 To Use Panel’s Printer Port Connection
Some FireWarden panels support data transfer through their printer terminal.
1. On the CLSS Gateway mainboard Side
• Connect the serial cable into the RS-232 port of the CLSS Gateway mainboard.
The RS-232 port is labeled as 6 in the Figure C.15.
2. On the Panel Side
Connect the serial cable in the DB9 serial port of the ANN-S/PG module on the panel.
3. Power Connection
On the CLSS Gateway mainboard Side
• Connect to the 24V DC external power supply.
• Switch the S7 Switch next to the RS-232 port towards NUP_OUT.
Figure C.14: The S7 Switch
On the Panel Side
Connect the power cable to a 24V DC external power source or the panel’s power
supply.
NOTE: Compatible CGW-MB firmware versions: 2.1.11.16 and above
CAUTION: ENSURE THAT ONLY THE ANN-S/PG IS CONNECTED AND NOT THE CGW-MB. ONLY ONE OF
THESE TWO CAN BE CONNECTED. BOTH OF THEM MUST NOT BE CONNECTED TOGETHER.