CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022 60
Register Mapping Modbus Communications
7.21.2 Point Device Type Input Registers
There are 6000 point device type holding registers. Each register address consists of two
bytes representing a detector or module.
400301 400600 L1M1–L1M300
400601 400900 L2D1–L2D300
400901 401200 L2M1–L2M300
401201 401500 L3D1–L3D300
401501 401800 L3M1–L3M300
401801 402100 L4D1–L4D300
402101 402400 L4M1–L4M300
402401 402700 L5D1–L5D300
402701 403000 L5M1–L5M300
403001 403300 L6D1–L6D300
403301 403600 L6M1–L6M300
403601 403900 L7D1–L7D300
403901 404200 L7M1–L7M300
404201 404500 L8D1–L8D300
404501 404800 L8M1–L8M300
404801 405100 L9D1–L9D300
405101 405400 L9M1–L9M300
405401 405700 L10D1–L10D300
405701 406000 L10M1–L10M300
Table 7.15: Point Status Holding Register Channel Addresses (Continued)
NOTE: On the AFP-2800, output activation status is not reported to the CGW-MB and
therefore the bits and event type will always indicate a non-active state.
NOTE: If the point is not present in the panel programming, all bits in the byte will contain
a value of 1 or FFFFH.
Table 7.16: Point Device Type Input Register Bit Definitions
Upper Byte Lower Byte
Bit
No.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Device Types (see
7.30 "Device Types"
)
Table 7.17: Input Register Addresses of the Point Device Types
Start
Address
End
Address
Address
300001 300300
L1D1–L1D300
300301 300600 L1M1–L1M300
300601 300900 L2D1–L2D300
300901 301200 L2M1–L2M300
301201 301500 L3D1–L3D300
301501 301800 L3M1–L3M300